Changelog

All notable changes to this project will be documented in this file.

The format is based on Keep a Changelog, and this project adheres to Semantic Versioning.

[Unreleased]

New

Changed

Fixed

0.4.3 - 2026-04-28

Changed

  • Battery and environment temperature graphs now also render as filled areas

0.4.2 - 2026-04-28

Changed

  • Single-metric graphs with a meaningful zero baseline (battery charge, battery voltage, output load, output power, environment humidity, alarm counters) now render as filled areas instead of lines

0.4.1 - 2026-04-15

0.4.0 - 2025-12-11

New

  • Added UPS Environment service for THS environmental sensor monitoring:
    • Temperature monitoring (thsOneTempData - .1.3.6.1.4.1.44782.1.2.1.1.1.0)
    • Humidity monitoring (thsOneHumiData - .1.3.6.1.4.1.44782.1.2.1.1.2.0)
    • Configurable thresholds for both upper and lower limits
    • Service auto-discovered only when THS sensor is connected
  • Added graphing metrics for environmental data (env_temperature, env_humidity)
  • Added environment-specific graphs (temperature, humidity, combined)

0.3.1 - 2025-09-09

Changed

  • UPS Battery Status service now only shows battery status and alarms (charge and runtime moved to dedicated services)
  • UPS System Info service now displays all key information in the summary instead of notices:
    • Model, manufacturer, and serial number shown in main summary
    • Firmware and agent versions displayed in summary
    • Power ratings and battery configuration visible at a glance
    • Maintenance expiration dates trigger warnings when overdue
  • UPS Battery Temperature service name corrected from "UPS Temperature"

Fixed

  • Removed duplicate battery charge and runtime metrics from Battery Status service
  • System Info service now provides comprehensive visibility of all system details

0.3.0 - 2025-09-09

New

  • Added individual battery monitoring services:
    • UPS Battery Charge - Dedicated service for battery charge percentage
    • UPS Battery Runtime - Dedicated service for remaining runtime
  • Added comprehensive graphing definitions with unit-based grouping:
    • Separated voltage graphs (AC voltages, battery voltage, all voltages)
    • Individual graphs for percentages, time metrics, currents, and temperature
    • Added missing metrics: battery_current, time_on_battery
  • Expanded physical measurement services to 13 individual monitors:
    • Input/Output/Bypass/Battery voltages
    • Input/Output/Bypass frequencies
    • Battery/Output currents
    • Temperature, Output power, Output load

Changed

  • Reorganized graphing to group metrics by unit type for better visualization
  • Updated ruleset configuration to support all 18 services with appropriate thresholds
  • Improved monitored_oids.md documentation with service-based organization
  • Made all ruleset parameters optional for flexible configuration
  • Enhanced battery voltage service to use device configuration as dynamic defaults

Fixed

  • Fixed temperature metric name (changed from battery_temperature to temperature)
  • Corrected ruleset parameter names to match check plugin expectations
  • Added missing threshold parameters for bypass voltage, battery voltage, currents, and power

0.2.0 - 2025-09-08

New

  • Added support for ALL OIDs from monitored_oids.md:
    • upsSecondsOnBattery (.1.3.6.1.2.1.33.1.2.2.0)
    • upsBatteryCurrent (.1.3.6.1.2.1.33.1.2.6.0)
    • upsInputNumLines (.1.3.6.1.2.1.33.1.3.2.0) - displayed in info service
    • upsOutputNumLines (.1.3.6.1.2.1.33.1.4.3.0) - displayed in info service
    • upsSmartBatteryRunTimeRemaining (.1.3.6.1.4.1.935.1.1.1.2.2.4.0) - alternative runtime metric
    • upsBaseOutputStatus (.1.3.6.1.4.1.935.1.1.1.4.1.1.0) - detailed output status with 15 states
    • ups1powerSupplyMode (.1.3.6.1.4.1.44782.1.4.4.1.39.0)
    • ups1remainingCapacityOfBattery (.1.3.6.1.4.1.44782.1.4.4.1.18.0)
  • Added enterprise battery voltage OID (.1.3.6.1.4.1.44782.1.4.4.1.19.0) as primary source

Changed

  • Improved handling of special SNMP value -99998 (indicates unknown/unavailable)
  • All converter functions now properly handle -99998 and return -1 for unknown values
  • Battery runtime and charge now display "unknown" instead of crashing when unavailable

Fixed

  • Fixed crash when battery runtime returns negative values (-99998)
  • Fixed parsing of enterprise voltage OIDs to handle -99998 special value
  • Battery check now gracefully handles unknown charge percentage and runtime

0.1.5 - 2025-09-08

Fixed

  • use HostCondition since we have no service items

0.1.4 - 2025-09-08

Fixed

  • return one unified rule

0.1.3 - 2025-09-08

0.1.2 - 2025-09-08

Fixed

  • fixed package nameing to contain oposs prefix

0.1.1 - 2025-09-08

Changed

  • Refactored SNMP OID handling to use metadata-driven approach with OIDDefinition dataclass
  • Improved code maintainability by centralizing OID configuration, scaling functions, and value mappings

Fixed

  • Noted mkp installation in README.md

0.1.0 - 2025-09-08